Products - KIMMCO Clean Liner (KCL)
 

 Applications

KIMMCO Clean Liner is used to line air conditioning ducts, walls and/or ceilings of acoustical sensitive areas to provide efficient sound insulation for any variety of structures, and/or sensitive facilities as home theatres, studios or curtain walls.

Descriptions

KIMMCO Clean Liner is a high efficient acoustic material, produced from strong resilient glass fibers firmly bounded together with a thermosetting resin.

Standard Dimensions Nominal Density
Thickness Width Length
Roll Board
15mm
25mm
40mm
50mm
1.2m 20m 1m

Other dimensions available

KCL kg/m3 lbs/ft3
16 16 1.0
24 24 1.5
32 32 2.0
48 48 3.0
60 60 3.75

Other densities available

Facings

KIMMCO Clean Liner is faced with a black, strong durable, dimensionally stable woven glass fabric.

Fiber Migration

KIMMCO Clean Liner achieves ZERO fiber migration.

Thermal Performance

Tested in accordance with ASTM C518.

Thermal Conductivity (W/m.K) Thermal Conductivity Btu.in/ft2.h.°F
Mean Temp. KCL 16  KCL 24 KCL 32 KCL 48 KCL 60 KCL 72
0 ºc
10 ºc
25 ºc
50 ºc
75 ºc
100 ºc
0.034
0.036
0.039
0.044
0.051
0.0057
0.031
0.032
0.035
0.039
0.043
0.047
0.030
0.031
0.033
0.037
0.040
0.044
0.029
0.030
0.031
0.035
0.037
0.041
0.030
0.031
0.032
0.036
0.038
0.042
0.031
0.033
0.035
0.037
0.040
0.043
Mean Temp. KCL 16  KCL 24 KCL 32 KCL 48 KCL 60 KCL 72
32 ºf
50 ºf
77 ºf
122 ºf
167 ºf
212 ºf
0.23
0.25
0.27
0.31
0.35
0.40
0.21
0.22
0.24
0.27
0.30
0.33
0.20
0.21
0.23
0.25
0.27
0.30
0.20
0.21
0.22
0.24
0.26
0.29
0.21
0.21
0.23
0.24
0.26
0.29
0.21
023
0.23
0.26
0.28
0.30
 
Acoustical Performance

KIMMCO Clean Liner is especially designed to provide exceptional sound absorption to acoustically sensitive environments and/or equipments as air-conditioning equipments, auditoriums, theatres, studios, acoustical building assemblies, curtain walls.

 

Product Thickness
mm
Absorption coefficients at one third octave band center frequencies (Hz) 
Type   125 250 500 1000 2000 4000  NRC
KCL 16 25 0.09 0.24 0.49 0.85 0.83 0.77 0.60
50 0.34 0.59 0.93 0.94 0.94 0.98 0.85
KCL 24 25 0.12 0.32 0.70 0.93 0.95 0.99 0.75
50 0.27 0.69 1.01 1.07 1.06 1.05 0.95
KCL 32 15 0.05 0.13 0.32 0.65 0.79 0.93 0.45
25 0.29 0.45 0.77 1.00 0.93 0.56 0.80
50 0.37 0.92 1.04 1.14 1.13 1.01 1.05
KCL 48 15 0.05 0.12 0.29 0.51 0.68 0.80 0.40
25 0.22 0.52 0.73 0.98 1.02 1.00 0.80
50 0.30 0.85 1.03 1.07 1.06 1.00 1.00
KCL 60 25 0.06 0.19 0.62 0.83 0.90 0.95 0.65
50 0.21 0.75 1.00 1.00 1.00 0.95 0.95

Test in accordance with ASTM C 423 using Type A mounting as per ASTM E 795. These are typical values subject to normal manufacturing and testing variances.

Physical Performances
 
  Properties   Performances   Test Method
  Operating temperature limits   Maximum:
  230 ºC
  ASTM C 411
  Surface Burning Characteristics

  (Fire Hazard Classification)

  Flame spread not over 25

  Smoke developed not over 50
  NFPA 255
  UL 723
  ASTM E 84
  Fire Classification   Class 0   BS 476 parts 6,7
  Water Vapor Absorption   Not Greater than 1% by volume   ASTM C 1104
  Fungi resistance
  Bacteria resistance
  Does not breed or promote growth   ASTM C 1071
  Air Velocity Rating

  Air Erosion  Rating
  25.4m/s
  (5.000 ft/minute)
  NIL at 63.5 m/s
  (12,500 ft/minute)
  UL 181
 
Conformity to Standards

KIMMCO Rigid Pipe Coverings comply with the following Standards:

American Standards

ASTM C 167, 168, 177, 411, 423, 518, 665 § 13.8 & 13.9, 1071, 1101/1101M, 1104/1104M 1335, 1338; E 84, 336, 477, 795, 1376 UL 181, 723 F.S. HH-1-545B NFPA 255, NFPA 90A & 90B NAIMA Standards SMACNA Standards ASHARE 90.1 requirements

British Standards

BS 476 (parts 4 & 6), 874, 2972, 3533, 3600, 3958 (part 5), 5643, 5720

German Standards

DIN 18165,52612

IS0

354, 8301, 8302, 9229, 9291

 
logo_kimmco2.gif
Alghanim Industries Industrial Group invited to provide its expertise at recently held "Future Airport" Conference, Dubai
KIMMCO promoting Glass wool and Stone wool insulation at Project Qatar
KIMMCO promotes safety with the KAIZEN week
KIMMCO educates the market
KIMMCO INSULATION grows with the Big 5 Show 2008
KIMMCO efforts rewarded by Kuwaiti Ministry of Public Works
KIMMCO seeks synergies at the Kuwait Contractors Exhibition and Conference
KIMMCO - ISOVER Conference on Insulation, Dubai
  
  
Best viewed on Internet Explorer 6.0 and Netscape 6.1 and above.
Copyright © 2003 - 2009 Alghanim Industries and Yusuf A. Alghanim & Sons w.l.l. | Terms & Conditions